HS06V-Q

6kW


Heating A+7 / W 35°C:

  • Heating capacity norm: 6,46 kW
  • Power consumption: 1,44 kW
  • COP: 4,49

 

Heating A+7 / W 55°C:

  • Heating capacity norm: 5,72 kW
  • Power consumption: 1,77 kW
  • COP: 3,23

 

Heating A+2 / W 35°C:

  • Heating capacity norm: 5,16 kW
  • Power consumption: 1,41 kW
  • COP: 3,66

 

 

ErP Heating:

  • Seasonal energy efficiency (W 35°C / W 55°C): 188,7 / 145,3 %
  • Energy efficiency rating (W 35°C / W 55°C): 4,79 / 3,70 SCOP
  • Seasonal energy efficiency (W 35°C / W 55°C): A+++ / A++

 

Refrigerant:

  • Type: R290
  • GWP: 3
  • Filing capacity: 0,6 kg
  • CO2 equivalent: 0,0018 ton


Features:

  • Outdoor sound power full load (heat): 57 dB(A)
  • Outdoor dimension (H*W*D): 850 x 1060 x 420 mm
  • Outdoor N / W: 92 kg
  • Operation range (Outdoor ambient): –25 ~ 46 °C
  • Water outlet (heat): 20 ~ 70 °C
  • Water outlet (cool): 5 ~ 20°C
  • Compressor type: TWIN ROTARY
  • Heat exchanger: Brazes Plate Heat Exchanger
  • Defrost method: Process reversal
  • Power control: Inverter control
  • Pipe connection Inlet / Outlet: External thread
  • Pipe diameter: 33,25 mm
  • Supply voltage: 1 ~
  • Frequency: 50 Hz
  • Voltage: 230 V
  • Voltage range Min. / Max.: -10 / +10 %
  • Working current (Max.) heating: 9 A
  • Recommended fuses: 10 A
  • Recommended cable size: 3 x 1,5 mm²
Share by: